小妖精又紧又湿高潮H视频69,少妇亚洲,欧美成人WWW免费全部网站,又色又爽又黄又刺激美女视频

產(chǎn)品中心您現(xiàn)在的位置:首頁(yè) > 產(chǎn)品展示 > SF6氣體檢測(cè)設(shè)備 > SF6氣體泄漏報(bào)警系統(tǒng)裝置 > 壁掛SF6氣體泄漏監(jiān)控報(bào)警系統(tǒng)

壁掛SF6氣體泄漏監(jiān)控報(bào)警系統(tǒng)

更新時(shí)間:2024-05-08

簡(jiǎn)要描述:

壁掛SF6氣體泄漏監(jiān)控報(bào)警系統(tǒng)系統(tǒng)內(nèi)有4個(gè)定時(shí)啟動(dòng)的時(shí)間,可根據(jù)用戶的要求設(shè)定0~4次定時(shí)啟動(dòng)、每次啟動(dòng)的具體時(shí)間與時(shí)長(zhǎng);

壁掛SF6氣體泄漏監(jiān)控報(bào)警系統(tǒng)

SHXL-3019壁掛SF6氣體泄漏監(jiān)控報(bào)警系統(tǒng)采用主動(dòng)吸氣方式,當(dāng)采樣氣體中含有SF6氣體時(shí),能夠通過(guò)檢測(cè)氣室的紅外光的強(qiáng)度將相應(yīng)減弱,根據(jù)減弱的幅度,運(yùn)用朗伯--比爾吸收定律可以計(jì)算出SF6氣體濃度。

主要功能
   1、實(shí)時(shí)顯示SF6氣體濃度系統(tǒng)循環(huán)采集被檢測(cè)區(qū)域的空氣,在操作控制屏及后臺(tái)監(jiān)控計(jì)算機(jī)上顯示該采樣空氣的SF6含量濃度;告警濃度可按要求在現(xiàn)場(chǎng)設(shè)定。
   2、實(shí)時(shí)顯示氧氣濃度
檢測(cè)主機(jī)內(nèi)含有氧氣檢測(cè)傳感器,在檢測(cè)各區(qū)域采樣氣體中SF6氣體的含量同時(shí),檢測(cè)氧氣含量,在操作控制屏及后臺(tái)監(jiān)控計(jì)算機(jī)上顯示該采樣空氣中的氧氣濃度;告警濃度可按要求在現(xiàn)場(chǎng)設(shè)定。
   3、告警輸出
當(dāng)SF6氣體或氧氣含量達(dá)到告警濃度時(shí),操作控制屏將按設(shè)定的方式,產(chǎn)生聲光、語(yǔ)音報(bào)警,并通過(guò)軟件規(guī)約或干接點(diǎn)通知遠(yuǎn)端監(jiān)控中心,同時(shí)按設(shè)定的方式啟動(dòng)風(fēng)機(jī)。
   4、紅外感應(yīng)與語(yǔ)音報(bào)警和提示
如果有工作人員接近開關(guān)時(shí)室,操作控制屏內(nèi)的紅外感應(yīng)被觸發(fā),操作控制屏將啟動(dòng)語(yǔ)音提示,通知提示工作人員當(dāng)前室內(nèi)是否有SF6或氧氣報(bào)警,并提示應(yīng)啟動(dòng)風(fēng)機(jī)通風(fēng)后進(jìn)入。
   5、風(fēng)機(jī)控制
風(fēng)機(jī)有定時(shí)啟動(dòng)、告警啟動(dòng)與強(qiáng)制啟動(dòng)三種方式;系統(tǒng)內(nèi)有4個(gè)定時(shí)啟動(dòng)的時(shí)間,可根據(jù)用戶的要求設(shè)定0~4次定時(shí)啟動(dòng)、每次啟動(dòng)的具體時(shí)間與時(shí)長(zhǎng);
當(dāng)SF6或氧氣濃度達(dá)到告警濃度時(shí),可根據(jù)用戶要求,設(shè)定系統(tǒng)是否啟動(dòng)風(fēng)機(jī)進(jìn)行通風(fēng);操作控制屏有風(fēng)機(jī)開與風(fēng)機(jī)關(guān)2個(gè)按紐,可以用來(lái)強(qiáng)制風(fēng)機(jī)啟動(dòng)或關(guān)閉;
   6、溫濕度顯示
溫度顯示范圍:-40~60℃      濕度顯示范圍:0~100%RH
   7、聲光報(bào)警控制
可根據(jù)用戶要求,聲光報(bào)警在啟動(dòng)后一定時(shí)間內(nèi)自動(dòng)關(guān)閉,以免影響周圍居民;

技術(shù)指標(biāo)
   1、SF6濃度檢測(cè)
    檢測(cè)范圍:≥100uL/L (即ppm);
   檢測(cè)精度:±10uL/L;
   檢測(cè)速度:≤2分鐘(30米測(cè)量距離);
   檢測(cè)方法:使用標(biāo)準(zhǔn)物質(zhì)研究中心提供的、用空氣與SF6氣體混合的標(biāo)準(zhǔn)氣體;
   2、氧氣檢測(cè)
   檢測(cè)范圍:0~25%;
   檢測(cè)精度:≤5%;
   3、溫度
   檢測(cè)范圍:-40~60℃;
   檢測(cè)精度:≤2℃;
   4、濕度
   壁掛SF6氣體泄漏監(jiān)控報(bào)警系統(tǒng)檢測(cè)范圍:0~100% RH;
   檢測(cè)精度:≤5%;
   5、風(fēng)機(jī)啟動(dòng)響應(yīng)時(shí)間:≤2s
   6、工作電源:AC  150V~265V
   7、工作環(huán)境:操作控制屏與檢測(cè)主機(jī)-10~50℃,其他-40~60℃;
   8、功耗:< 60W
   9、抗電強(qiáng)度(外殼金屬部分與電源之間):>2000V
   10、絕緣性能(外殼金屬部分與電源之間);> 10MΩ
   11、風(fēng)機(jī)控制接觸器觸點(diǎn)功率:         AC220V/20A
   12、EMC特性:符合IEC1000-4標(biāo)準(zhǔn);
   13、通訊:
   接口:485接口
   規(guī)約:電總標(biāo)準(zhǔn)通信協(xié)議、IEC870-5-101或其他通訊協(xié)議
   波特率:9600BPS(出廠設(shè)定)

系統(tǒng)主要技術(shù)特性

工作環(huán)境··································-10-50℃, 環(huán)境濕度≤95%,海拔2000米以下
工作電源··································AC/DC 185-265V
功耗··········································主機(jī):<20VA 變送器:<5W
SF6氣體泄漏報(bào)警值·················缺?。?000ppm,可根據(jù)需求執(zhí)行設(shè)置報(bào)警誤差<5%(V/V)
氧含量檢測(cè)范圍······················0-25.0%(V/V), <0.5%(V/V) 低于18.0%報(bào)警
風(fēng)機(jī)啟動(dòng)······································································································································1.SF6氣體泄漏時(shí)自動(dòng)通風(fēng)2.氧氣含量≤18.0%時(shí)風(fēng)機(jī)自動(dòng)啟動(dòng)3.自動(dòng)定時(shí)排風(fēng)4.可手動(dòng)強(qiáng)制啟動(dòng)風(fēng)機(jī)排風(fēng)
··················································
溫度顯示范圍-20-99℃
濕度顯示范圍0-99%RH
報(bào)警輸出觸點(diǎn)功率··················AC220V/3A
風(fēng)機(jī)輸出觸點(diǎn)功率··················AC220V/3A(增加風(fēng)機(jī)控制器為30A)
絕緣性能··································>10MΩ(外殼與電源間)
抗電強(qiáng)度··································>2000V(外殼與電源間)
電磁兼容特性··························快速瞬變脈沖群 GB/T17626.4-1999 3級(jí)
··················································雷擊(浪涌) GB/T17626.5-1999 3級(jí)
變送器與主機(jī)通訊··················標(biāo)準(zhǔn)RS485接口,波特率4800BPS
RTU通訊···································標(biāo)準(zhǔn)RS485、RS232接口,波特率4800BP

第2章 基本操作指南

1、 開機(jī)

打開電源,主機(jī)進(jìn)入初始化。

2、 系統(tǒng)操作

1) 按鍵功能

u 共有“上"、“下"、“左"、“右"、“靜音"、“通風(fēng)"、“返回"、“確定"8個(gè)功能鍵,對(duì)應(yīng)8種操作,按下按鍵,聽(tīng)到蜂鳴器“吡"聲后,松開按鍵,繼續(xù)下一步操作。

u 屏幕下部各項(xiàng)功能菜單在反顯時(shí)處于激活狀態(tài),按“確定"進(jìn)入菜單功能,按“上"、“下"切換菜單。

u“靜音"取消提示音一小時(shí),一小時(shí)后恢復(fù)

u按“通風(fēng)"鍵,風(fēng)機(jī)工作工作15分鐘后自動(dòng)停止,在通風(fēng)時(shí)按下“通風(fēng)"鍵風(fēng)機(jī)停止

2) 采集數(shù)據(jù)

u采集周期設(shè)置默認(rèn)為1分鐘/次,可根據(jù)需要修改(1-30分鐘)。

u主界面下選中“即時(shí)采集"菜單按“確定"鍵,即可實(shí)時(shí)采集數(shù)據(jù)。

3) 報(bào)警記錄查詢

u主界面下選中“報(bào)警記錄"菜單按“確定"鍵,可直接查詢報(bào)警記錄。

(按“返回"鍵返回主界面)

4) 歷史數(shù)據(jù)查詢

u主界面下選中“歷史數(shù)據(jù)"菜單按“確定"鍵,查詢歷史數(shù)據(jù)。(按“返回"鍵返回主界面)

3、 系統(tǒng)設(shè)置(非系統(tǒng)維護(hù)人員,請(qǐng)勿進(jìn)入“系統(tǒng)設(shè)置")

u 選擇按鍵“系統(tǒng)設(shè)置",入密碼輸入窗口;

u 輸入正確密碼后按“確認(rèn)"鍵進(jìn)入,或者按“取消"鍵退出;

(密碼按四下“上"鍵)

u 輸入正確密碼進(jìn)入系統(tǒng)設(shè)置窗口后,通過(guò)“上"鍵或“下"鍵選擇修改項(xiàng),按“確認(rèn)"鍵,進(jìn)入相應(yīng)操作界面。

u 按“上"鍵或“下"鍵可對(duì)所選中的系統(tǒng)時(shí)鐘、定時(shí)排風(fēng)啟停時(shí)間等進(jìn)行設(shè)置,通過(guò)“左"鍵或“右"鍵選擇域,最后按“確認(rèn)"鍵保存修改,選中“返回"放棄修改;

u 進(jìn)行“確認(rèn)"或“取消/返回"功能操作后系統(tǒng)回到主菜單選擇界面。

注意:非系統(tǒng)維護(hù)人員,請(qǐng)勿進(jìn)入“系統(tǒng)設(shè)置"。

第3章

系統(tǒng)組成示意圖

系統(tǒng)結(jié)構(gòu)示意

系統(tǒng)的連接與安裝

● 系統(tǒng)主機(jī):屏柜式或壁掛式。一般安裝于主控室內(nèi)專用屏柜上或開關(guān)室門口,高度以便于觀察顯示窗且便于操作為宜,連接AC220V電源及通訊電纜、警燈及風(fēng)機(jī)控制輸出。

● SF6氣體采集器一般根據(jù)氣室分布情況進(jìn)行布點(diǎn),安裝于距地面0—250px的槽鋼或地面上,使之既要保障能及時(shí)監(jiān)測(cè)現(xiàn)場(chǎng)環(huán)境情況,又不浪費(fèi)設(shè)備資源。

● 所有數(shù)據(jù)連接線應(yīng)采用屏蔽電纜?!?/p>

留言框

  • 產(chǎn)品:

  • 您的單位:

  • 您的姓名:

  • 聯(lián)系電話:

  • 常用郵箱:

  • 省份:

  • 詳細(xì)地址:

  • 補(bǔ)充說(shuō)明:

  • 驗(yàn)證碼:

    請(qǐng)輸入計(jì)算結(jié)果(填寫阿拉伯?dāng)?shù)字),如:三加四=7
上海蘇霍電氣有限公司

上海蘇霍電氣有限公司

專業(yè)提供壁掛SF6氣體泄漏監(jiān)控報(bào)警系統(tǒng)等產(chǎn)品信息,歡迎來(lái)電咨詢!

地址:上海市寶山區(qū)一二八紀(jì)念路968號(hào)1205-A18室

版權(quán)所有:上海蘇霍電氣有限公司  備案號(hào):滬ICP備19018078號(hào)-1  總訪問(wèn)量:291569  站點(diǎn)地圖  技術(shù)支持:化工儀器網(wǎng)  管理登陸

QQ在線客服
聯(lián)系方式

13661938492

86-021-31262198